GW5 Outdoor HV Disconnect Switch

GW5 outdoor high voltage disconnect switch is used to make or break high
voltage circuit in rated voltage 40.5kV,72.5kV or 126/145kV, AC 50/60Hz
system, It is also used to open and close small capacitanc e and induct ive
current. This series disconnect switch accord with standards: GB1985 AC High
voltage disconnect switch and earthing switch, IEC60129 AC disconnect switch
and earthing switch and GB/T11022 Common technical requi rements of HV
switchgear and control equipment.

Ambient condition

  1. Altitude: ≤3000m;
  2. Ambient temperature: -25℃ ~+40℃ ;
  3. Wind speed: ≤35m/s;
  4. Pollution degree: ≤III;
  5. Earthquake intensity: ≤8 degree;
  6. Ice thickness: ≤10mm.

Model

Structure feature

  1. Adopt roll bearing to keep flexible driving.
  2. Adopt umbrella-gear wheel mechanism to ensure O/C operating congruously.
  3. There is an direction-limited device to ensure the contactor under good direction, at the same time, the handcr aft
    was fastened after operating to ensure the security performance.
  4. Contact distance is large enough.
  5. There are three type earth method, without earth, single earth, double earth.

Technical specification

      Item      Model    Rated voltage (kV)    Rated current (A)Disconnect switchEarthing switch    Earth
  Withstand current (kA)Short-time withstand current(kA)Withstand current (kA)Short-time withstand current (kA)
      
    General type Anti-pollution type  40.5 GW5-72.5II 12 6/145 (D, DW)    40.5 72.5 126/145630  50  20(4s)      50      80      20 (4s)      31.5 (4s)  Without earth single earth double earth
1000
1250  8031.5(4s)
160031.5(4s)

Structure feature

There are two supporting insulators fixuped on the pedestals respectively with the 50℃ inclinat ion, and the main components
include pedestals, supporting insulators, connection seat, contacts earthing blades, earthing fixed contact and so on. There are
three kinds of disconnect switch: without earthing, single-earthing and double-earthing. It be provided with mechanism linkage
between principal axis and earthing blades and assistant switch, operating can be achieved by manual and motor.

Outline dimension

GW5-110/132126/145~2000~2800~1473~1569~1533~1362
GW5-3540.5~1200~1600~830~1000~845~700
ModelRoted voltage(kV)L1(mm)L2(mm)L3(mm)L4(mm)L5(mm)L6(mm)

1.GW5 single pole disconnect swith 2.Universal coupling 3.pin 4.Opening pin 3 20 5.1¼ water gas pipe(inner dia 32mm) 6.lock
7.Slot 8.Pin 9.CS17 operating mechanism by manual 10.Hexagonal nut M12 11.Washer 12 12.Washer 12 13.Hexagonal bolt M12×30
14.Frame 15.Pin 16. ¾(35kV)(inner dia 20mm) or 1(110kV)(inner dia 25mm) 17.Jointing connection-board 18.Nut M16 19.Washer 16
20.Screw 21.Terminal 22.Slot 23.Solt 10 24.anchor ear 25.1½ Water gas pipe(inner dia 40mm) 26.Angle iron 63×63×6(220mm)
27.Angle iron 63×63×6(180mm)

Popular Products

  • SFAI (Air Type)(Smart Fault Automatic Interrupter) 

    ORC unit of the new design, which solve the mobility caused by ageing, provides the reliable circuit interruption performance without external arc of flame and completely prevents the switch from the arc caused by switching the load currents 400/ 630A at rated voltage

    Learn More
  • GN30-12(D)Rotary Indoor AC HV Disconnect Switch

    GN30-12(D) disconnec t switch is an indoor electric apparatus of rated voltage
    12kV, three-phase AC50/60Hz. It is used to make break and transfer current
    for HV ele ctric apparatus under situations with voltage and no-load.

    Learn More